Industrial & Commercial Energy Storage Cabinet GCB-E240
- 241 kWh / 125 kW
- LFP 314Ah
- IP54
- Three-Phase
Send us your load list and we size it.
High-capacity 241 kWh / 125 kW outdoor energy storage cabinet with integrated PCS, fire protection and air-cooling. Built for commercial and industrial peak shaving, demand charge management and backup power.
Best for: Higher-power commercial and industrial peak shaving and demand control
Key Specifications
Battery Parameters
| Battery Type | LFP 314/280Ah |
|---|---|
| Battery Pack | 51.2V 314Ah |
| Rated Voltage | 768 V (15 module series) |
| Rated Energy | 241.15 kWh nominal (314 Ah pack) / 215.04 kWh nominal (280 Ah pack) |
| DOD | 95% |
| Cycle Life | 6000 cycles at 0.25C, 95% DOD, 25 °C |
| Voltage Range | 672 – 864 V |
Operational Parameters
| Rated Charge / Discharge Power | 125 kW |
|---|---|
| Integrated PCS | Three-phase hybrid, grid-tied (PCS mass not included in the cabinet weight) |
| Grid Type | Three-Phase Four-Wire |
| Rated Grid Voltage | AC 380 V |
| Applicable Grid Frequency | 50 Hz |
| Rated Current | 189 A |
| Current Harmonic Distortion | <3% |
| Power Factor Range | 1 (leading) ~ 1 (lagging) |
| Operating Temperature Range | -20 ~ 50 ℃ |
| Relative Humidity | 0 – 95% |
| Altitude | <2000 m |
| Cooling Method | Air cooling (refrigeration, ventilation, heating) |
| Noise | ≤75 dB |
System Parameters
| System Efficiency | ≥90% |
|---|---|
| Fire Protection System | Integrated |
| Messaging | RS485 / CAN |
| Ingress Protection | IP54 |
| Dimension (W×D×H) | 1300 × 1260 × 2375 mm |
| Weight | 2500 kg (excluding PCS) |
Where It Fits
- Factories and campuses managing a demand charge
- Sites with a sharp morning or evening peak
- Backup for a line that cannot drop
- PV self-consumption on a commercial roof
Compatible Equipment
Three-phase four-wire AC 380 V at 50 Hz, RS485 / CAN, Modbus TCP/IP to a site SCADA.